Question 1
An elevated storage tank holds a column of water 100 feet tall. Ignoring all other factors, what static pressure does that column exert at its base?
Show answer & explanation
Correct answer: C - 43.3 psi
10 free, exam-style Backflow Prevention Assembly Tester (BPAT) practice questions with answers and explanations. No signup required. Work through them below, then take the full free BPAT practice test to study every exam domain.
These 10 free BPAT questions are organized by exam domain, so you can see how each part of the Backflow Prevention Assembly Tester blueprint is tested. Reveal the answer and explanation under each question.
An elevated storage tank holds a column of water 100 feet tall. Ignoring all other factors, what static pressure does that column exert at its base?
Correct answer: C - 43.3 psi
A landscape irrigation system injects liquid fertilizer (a health hazard) into the line, and a downstream booster pump can raise pressure above the supply main. What is the MINIMUM assembly that provides proper protection?
Correct answer: D - Reduced pressure principle assembly (RP)
Which backflow prevention assembly consists of two independently acting check valves PLUS a hydraulically operated differential pressure relief valve located between them?
Correct answer: A - Reduced pressure principle assembly (RP)
An atmospheric vacuum breaker (AVB) has been installed with a shut-off valve downstream of it, leaving the AVB under constant supply pressure. What is the PRIMARY problem with this installation?
Correct answer: A - Under continuous pressure the air-inlet poppet can stick closed and fail to open
A high-hazard cross-connection is subject to backsiphonage only (no backpressure is possible) and is located indoors, where any discharge of water from the assembly would be unacceptable. Which assembly is the BEST choice?
Correct answer: D - Spill-resistant vacuum breaker (SVB)
When field-testing a reduced pressure principle assembly (RP), what are the minimum acceptable values for the differential relief valve opening point and the first check valve?
Correct answer: B - Relief valve opens at 2.0 psid; first check holds 5.0 psid
Following the standard USC procedure for a double check valve assembly (DC), which check valve is tested FIRST, and why?
Correct answer: C - Check valve No. 2, to keep trapped air from causing an inaccurate reading on check valve No. 1
While testing an RP, a tester finds that the low-side control valve must be opened more than one-quarter turn before the relief valve will discharge. This MOST likely indicates:
Correct answer: B - A leaking No. 2 shut-off valve creating a flow-through condition
When field-testing a pressure vacuum breaker (PVB) or spill-resistant vacuum breaker (SVB), where must the differential test kit be held to obtain accurate readings?
Correct answer: B - At the same elevation as the assembly being tested
Under the federal Safe Drinking Water Act, responsibility for the quality of the public water supply up to the consumer's service connection rests with which party?
Correct answer: C - The water purveyor (water supplier)
Practice hundreds more BPAT questions with instant scoring, weak-area drills, and full exam simulations.